Module 5 · Output
Quote scoping builder
Pick the class, tick what is on site, and get a structured schedule outline with the standards, frequency bands and Queensland paperwork — plus a site walk checklist you can work from in the carpark.
1. Building class
Passive doors are six-monthly for Class 5. QDC MP 6.1 applies to this class.
2. Assets present
Service schedule outline
Class 5 — Office
Fire hose reels
AS 1851-2012 · Section 9 · Design: AS 2441
Records: Tags, labels and summary records.
Licence: QBCC fire protection occupational licence — fire hose reels / water-based.
Portable and wheeled fire extinguishers
AS 1851-2012 · Section 10 · Design: AS 2444 (selection and placement); AS 2337 (cylinder testing)
Records: Tags, labels and summary records.
Licence: QBCC fire protection occupational licence — portable fire equipment.
Emergency and exit lighting
AS/NZS 2293.2:1995 — NOT AS 1851 · Design: AS/NZS 2293.1 (design and installation)
Records: Emergency lighting logbook and records per AS/NZS 2293.2.
Licence: Electrical licence; QBCC licensing as applicable to the installation work.
Procedures and pass/fail criteria are in the licensed standard. FVS technicians work from the controlled copy.
Queensland paperwork triggered
- No water-based installations selected — Form 71/72 not triggered.
- Occupier statement support — annual Schedule 2 statement, asset list, critical defect notices and proof of rectification attached.
- Logbooks and service or summary records maintained on site for every system in scope.
Site walk checklist
Photograph
- Booster assembly and its block plan
- Fire indicator panel, including the manufacture date plate
- Valve room / sprinkler valve set and gauges
- Pump room: controller, batteries, fuel tank
- One example of each fire door tag and frame tag
- One extinguisher tag and its location signage
- Hose reel cabinet and any obstructions
- Exit and emergency luminaires in the main path of travel
- Damper access panels and any ceiling obstructions
- Any visible defect, with something in frame for scale
Ask for
- Certificate of classification
- Last occupier statement (and the one before it)
- Logbooks for each system, including the emergency lighting logbook
- Any fire engineering report
- Alternative solution / performance solution documentation
- Last Form 72 for hydrants and sprinklers
- Any critical defect notices and proof of rectification
- Damper register and rolling 20% schedule
- Current provider's licence numbers by discipline
- Building age and date of the development application approval
Copyable summary for email or estimating
FVS SCOPING SUMMARY — Class 5 (Office)
Jurisdiction: Queensland · QDC MP 6.1 applies
SERVICE SCHEDULE OUTLINE
- Fire hose reels
Governing standard: AS 1851-2012 (Section 9)
Design/install: AS 2441
Frequency bands: Six-monthly, Yearly
Records: Tags, labels and summary records.
Licence: QBCC fire protection occupational licence — fire hose reels / water-based.
- Portable and wheeled fire extinguishers
Governing standard: AS 1851-2012 (Section 10)
Design/install: AS 2444 (selection and placement); AS 2337 (cylinder testing)
Frequency bands: Six-monthly, Yearly, Five-yearly
Records: Tags, labels and summary records.
Licence: QBCC fire protection occupational licence — portable fire equipment.
- Emergency and exit lighting
Governing standard: AS/NZS 2293.2:1995 — NOT AS 1851
Design/install: AS/NZS 2293.1 (design and installation)
Frequency bands: Six-monthly, Yearly
Records: Emergency lighting logbook and records per AS/NZS 2293.2.
Licence: Electrical licence; QBCC licensing as applicable to the installation work.
QLD note: In Queensland, MP 6.1 A1(c) requires emergency lighting maintenance to comply with AS/NZS 2293.2:1995 — it is expressly excluded from the AS 1851 acceptable solution. Quoting emergency lighting under AS 1851 is the classic new-BDM mistake.
QUEENSLAND PAPERWORK TRIGGERED
- No water-based installations selected: Form 71/72 not triggered.
- Occupier statement support: annual Schedule 2 statement, asset list and attachments.
- Logbooks and service/summary records maintained on site for each system.
SITE WALK — PHOTOGRAPH
- Booster assembly and its block plan
- Fire indicator panel, including the manufacture date plate
- Valve room / sprinkler valve set and gauges
- Pump room: controller, batteries, fuel tank
- One example of each fire door tag and frame tag
- One extinguisher tag and its location signage
- Hose reel cabinet and any obstructions
- Exit and emergency luminaires in the main path of travel
- Damper access panels and any ceiling obstructions
- Any visible defect, with something in frame for scale
SITE WALK — ASK FOR
- Certificate of classification
- Last occupier statement (and the one before it)
- Logbooks for each system, including the emergency lighting logbook
- Any fire engineering report
- Alternative solution / performance solution documentation
- Last Form 72 for hydrants and sprinklers
- Any critical defect notices and proof of rectification
- Damper register and rolling 20% schedule
- Current provider's licence numbers by discipline
- Building age and date of the development application approval
General guidance only. Not legal advice. Confirm against the certificate of classification, any fire engineering report or alternative solution, and the current licensed standards before quoting. Procedures and pass/fail criteria are in the licensed standard.