QLD

Module 5 · Output

Quote scoping builder

Pick the class, tick what is on site, and get a structured schedule outline with the standards, frequency bands and Queensland paperwork — plus a site walk checklist you can work from in the carpark.

1. Building class

Passive doors are six-monthly for Class 5. QDC MP 6.1 applies to this class.

2. Assets present

Service schedule outline

Class 5Office

Fire hose reels

AS 1851-2012 · Section 9 · Design: AS 2441

Six-monthlyYearly

Records: Tags, labels and summary records.

Licence: QBCC fire protection occupational licence — fire hose reels / water-based.

Portable and wheeled fire extinguishers

AS 1851-2012 · Section 10 · Design: AS 2444 (selection and placement); AS 2337 (cylinder testing)

Six-monthlyYearlyFive-yearly

Records: Tags, labels and summary records.

Licence: QBCC fire protection occupational licence — portable fire equipment.

Emergency and exit lighting

AS/NZS 2293.2:1995 — NOT AS 1851 · Design: AS/NZS 2293.1 (design and installation)

Six-monthlyYearly

Records: Emergency lighting logbook and records per AS/NZS 2293.2.

Licence: Electrical licence; QBCC licensing as applicable to the installation work.

Procedures and pass/fail criteria are in the licensed standard. FVS technicians work from the controlled copy.

Queensland paperwork triggered

  • No water-based installations selected — Form 71/72 not triggered.
  • Occupier statement support — annual Schedule 2 statement, asset list, critical defect notices and proof of rectification attached.
  • Logbooks and service or summary records maintained on site for every system in scope.
QDC MP 6.1 A2 / A3 / A4 / A5

Site walk checklist

Photograph

  • Booster assembly and its block plan
  • Fire indicator panel, including the manufacture date plate
  • Valve room / sprinkler valve set and gauges
  • Pump room: controller, batteries, fuel tank
  • One example of each fire door tag and frame tag
  • One extinguisher tag and its location signage
  • Hose reel cabinet and any obstructions
  • Exit and emergency luminaires in the main path of travel
  • Damper access panels and any ceiling obstructions
  • Any visible defect, with something in frame for scale

Ask for

  • Certificate of classification
  • Last occupier statement (and the one before it)
  • Logbooks for each system, including the emergency lighting logbook
  • Any fire engineering report
  • Alternative solution / performance solution documentation
  • Last Form 72 for hydrants and sprinklers
  • Any critical defect notices and proof of rectification
  • Damper register and rolling 20% schedule
  • Current provider's licence numbers by discipline
  • Building age and date of the development application approval

Copyable summary for email or estimating

FVS SCOPING SUMMARY — Class 5 (Office)
Jurisdiction: Queensland · QDC MP 6.1 applies

SERVICE SCHEDULE OUTLINE
- Fire hose reels
    Governing standard: AS 1851-2012 (Section 9)
    Design/install: AS 2441
    Frequency bands: Six-monthly, Yearly
    Records: Tags, labels and summary records.
    Licence: QBCC fire protection occupational licence — fire hose reels / water-based.
- Portable and wheeled fire extinguishers
    Governing standard: AS 1851-2012 (Section 10)
    Design/install: AS 2444 (selection and placement); AS 2337 (cylinder testing)
    Frequency bands: Six-monthly, Yearly, Five-yearly
    Records: Tags, labels and summary records.
    Licence: QBCC fire protection occupational licence — portable fire equipment.
- Emergency and exit lighting
    Governing standard: AS/NZS 2293.2:1995 — NOT AS 1851
    Design/install: AS/NZS 2293.1 (design and installation)
    Frequency bands: Six-monthly, Yearly
    Records: Emergency lighting logbook and records per AS/NZS 2293.2.
    Licence: Electrical licence; QBCC licensing as applicable to the installation work.
    QLD note: In Queensland, MP 6.1 A1(c) requires emergency lighting maintenance to comply with AS/NZS 2293.2:1995 — it is expressly excluded from the AS 1851 acceptable solution. Quoting emergency lighting under AS 1851 is the classic new-BDM mistake.

QUEENSLAND PAPERWORK TRIGGERED
- No water-based installations selected: Form 71/72 not triggered.
- Occupier statement support: annual Schedule 2 statement, asset list and attachments.
- Logbooks and service/summary records maintained on site for each system.

SITE WALK — PHOTOGRAPH
- Booster assembly and its block plan
- Fire indicator panel, including the manufacture date plate
- Valve room / sprinkler valve set and gauges
- Pump room: controller, batteries, fuel tank
- One example of each fire door tag and frame tag
- One extinguisher tag and its location signage
- Hose reel cabinet and any obstructions
- Exit and emergency luminaires in the main path of travel
- Damper access panels and any ceiling obstructions
- Any visible defect, with something in frame for scale

SITE WALK — ASK FOR
- Certificate of classification
- Last occupier statement (and the one before it)
- Logbooks for each system, including the emergency lighting logbook
- Any fire engineering report
- Alternative solution / performance solution documentation
- Last Form 72 for hydrants and sprinklers
- Any critical defect notices and proof of rectification
- Damper register and rolling 20% schedule
- Current provider's licence numbers by discipline
- Building age and date of the development application approval

General guidance only. Not legal advice. Confirm against the certificate of classification, any fire engineering report or alternative solution, and the current licensed standards before quoting. Procedures and pass/fail criteria are in the licensed standard.

General guidance only, current as at the version dates shown. Not legal advice. Confirm requirements against the building's certificate of classification, any fire engineering report or alternative solution, and the current licensed standards before quoting.

Jurisdiction: Queensland. AS 1851-2012, AS/NZS 2293.2 and related standards are copyright Standards Australia — procedures and pass/fail criteria are not reproduced here. FVS technicians work from the controlled copy.